jjm-logo
Jal Jeevan Mission
PHED Assam
emblem
GOVERNMENT OF ASSAM
SINGRITOLI PWSS (Rev. of 305)
Singitali Gaon, Sonitpur
Public Health Engineering Department
Tezpur Division Division
Latest Water Supplied
Data Not Appropriate KL ()
Cumulative Water Supplied
N/A

Basic details of the scheme are enlisted here, for further information please contact concerned officer of division / sub division

About This Scheme

Name
SINGRITOLI PWSS (Rev. of 305)
Scheme ID
0008153823
Division
Tezpur Division
District
Sonitpur
Block

Panchayat

BALIPARA

SINGITOLI

Village

Habitation

Singitali Gaon

SINGRITOLI NORTH, SINGRITOLI NO.2, SINGRITOLI EAST, SINGRITOLI CENTRAL, SINGITALI, SINGRITOLI NO.1

Implementing Agency details of the scheme are enlisted here

About Scheme

Approved On
1st SLSSC | (2020-21)
No. of FHTC
0.00
Total Cost
1649000.00
State Share
156700.00
Central Share
1409900.00
Handed Over On
2022-12-15 00:00:00

About Implementing Agency

Name of Agency
M/S AARAVII
Work Order Date
-

Jal Mitra & WUC Users details of the scheme are enlisted here

About Jal Mitra

Name
Phone

About Section Officer

Name
Jahangir Alam
Phone
8638492199

Water Quality details of the scheme are enlisted here.

About Water Quality

Date of Testing
N/A
PH
N/A
TDS
N/A
Iron
N/A
Arsenic/Flouride
N/A
Residual Chlorine
N/A
Bacteriological Test
N/A

Component details of the scheme are enlisted here.

About Scheme Components

No data found.

Please click on button to view map.

Map

You need to login to evaluate a scheme.

Register

Login

Water Quality Test Report

Sample Tested Status

Total Samples Tested: 36

Chemical Testing Date: 12/13/2024 3:05:00 PM

Bacteriological Testing Date: 1/21/2025 3:10:00 PM

Water Quality Status: Safe

Remedial Action Status: --

Chemical Contamination Results

Parameter Unit Acceptable Limit Permissible Limit Value Range Status
Colour Hazen units 5 15 10.000

Safe :1

> 15 Safe
Turbidity NTU 1 5 0.500

Safe :1

> 5 Safe
TDS mg/l 500 2000 72.000

Safe :1

> 2000 Safe
Total Alkalinity (as Calcium Carbonate) mg/l 200 600 75.000

Safe :1

> 600 Safe
Chloride (as Cl) mg/l 250 1000 18.430

Safe :1

> 1000 Safe
Fluoride (as F) mg/l 1 1.5 0.263

Safe :1

> 1.5 Safe
Nitrate (as NO3) mg/l 45 No Relaxation 0.360

Safe :1

> 45 Safe
Sulphate (as SO4) mg/l 200 400 3.150

Safe :1

> 400 Safe
Calcium (as Ca) mg/l 75 200 0.000

Safe :1

> 200 Safe
Magnesium (As Mg) mg/l 30 100 0.000

Safe :1

> 100 Safe
Total Hardness (As CaCO3) mg/l 200 600 72.000

Safe :1

> 600 Safe
Iron (As Fe) mg/l 1 No Relaxation 0.124

Safe :1

> 1 Safe
Total Arsenic (As As) mg/l 0.01 No Relaxation 0.000

Safe :1

> 0.01 Safe
Free residual Chlorine mg/l 0.2 1 0.500

Safe :1

> 1 Safe

Bacteriological Contamination Results

Parameter Unit Acceptable Limit Permissible Limit Value Range Status
Total coliform CFU/ 100 ml Shall not be detectable in any 100 ml sample No Relaxation 0.000

Safe :1

Shall not be detectable in any 100 ml sample Safe

Sample Testing Results

Date Contaminated Found Remedial Action Location Status Taken
21-01-2025 Bacteriological Not required Source Safe
13-12-2024 Chemical and bacteriological both Yes Source Unsafe
14-08-2024 Chemical Not required Source Safe
30-05-2024 Chemical and bacteriological both Not required Source Safe
30-05-2024 Chemical and bacteriological both Yes Source Unsafe
30-05-2024 Chemical and bacteriological both Not required Individual Household Safe
30-05-2024 Chemical and bacteriological both Not required Individual Household Safe
05-02-2024 Chemical and bacteriological both Not required Source Safe
05-01-2024 Chemical and bacteriological both Not required Individual Household Safe
05-01-2024 Chemical and bacteriological both Not required Individual Household Safe
05-01-2024 Chemical and bacteriological both Not required Individual Household Safe
05-01-2024 Chemical and bacteriological both Not required Individual Household Safe
05-01-2024 Chemical and bacteriological both Not required Individual Household Safe
04-01-2024 Chemical and bacteriological both Not required Individual Household Safe
04-01-2024 Chemical and bacteriological both Not required Individual Household Safe
04-01-2024 Chemical and bacteriological both Not required Individual Household Safe
04-01-2024 Chemical and bacteriological both Not required Individual Household Safe
04-01-2024 Chemical and bacteriological both Not required Individual Household Safe
12-07-2023 Chemical and bacteriological both Not required Source Safe
12-07-2023 Chemical and bacteriological both Not required Source Safe
12-07-2023 Chemical and bacteriological both Not required Individual Household Safe
12-07-2023 Chemical and bacteriological both Not required Source Safe
12-07-2023 Chemical and bacteriological both Not required Individual Household Safe
12-07-2023 Chemical and bacteriological both Not required Individual Household Safe
12-07-2023 Chemical and bacteriological both Not required Individual Household Safe
12-07-2023 Chemical and bacteriological both Not required Individual Household Safe
12-07-2023 Chemical and bacteriological both Not required Individual Household Safe
12-07-2023 Chemical and bacteriological both Not required Individual Household Safe
12-07-2023 Chemical and bacteriological both Not required Individual Household Safe
12-07-2023 Chemical and bacteriological both Not required Individual Household Safe
11-07-2023 Chemical and bacteriological both Not required Source Safe
11-07-2023 Chemical and bacteriological both Not required Source Safe
17-06-2023 Chemical and bacteriological both Not required Source Safe
17-06-2023 Chemical and bacteriological both Not required Source Safe
25-11-2022 Chemical and bacteriological both Not required Source Safe
25-11-2022 Chemical and bacteriological both Not required Source Safe

Nearest Laboratory

Lab Name: DLL Sonitpur

Type: GOVT

Address: o/o The Executive Engineer (PHE) Tezpur Div No 1, Rubber Bagan, Tezpur, Assam, Pin: 784001

Scheme Network Map

You can follow us on:

How satisfied are you with the scheme?