jjm-logo
Jal Jeevan Mission
PHED Assam
emblem
GOVERNMENT OF ASSAM
Bhokot Puma PWSS
BHAKAT PAMUA, Jorhat
Public Health Engineering Department
Jorhat Division Division
Latest Water Supplied
39 KL (13-06-2025)
Cumulative Water Supplied
6819.00 KL

Basic details of the scheme are enlisted here, for further information please contact concerned officer of division / sub division

About This Scheme

Name
Bhokot Puma PWSS
Scheme ID
30182559
Division
Jorhat Division
District
Jorhat
Block

Panchayat

JORHAT

PACHIM KHONGIA

Village

Habitation

BHAKAT PAMUA

NAMONI BHOKOT PAMUA, NAMONI BHOKOT PAMUA DAKHIN CHUCK, NAMONI BHOKOT PAMUA MUSHI CHUCK, UJANI BHOKOT PAMUA CHUCK NO.2(TWO), UJANI BHOKOT PAMUA CHUCK NO.1(ONE)

Implementing Agency details of the scheme are enlisted here

About Scheme

Approved On
2nd SLSSC | (2022-23)
No. of FHTC
113.00
Total Cost
7158000.00
State Share
680010.00
Central Share
6120090.00
Handed Over On
2024-12-15 00:00:00

About Implementing Agency

Name of Agency
Manash Jyoti Bora
Work Order Date
2023-11-30

Jal Mitra & WUC Users details of the scheme are enlisted here

About Jal Mitra

Name
Binud Chowhan
Phone
9395037855

About WUC

WUC Name
UJJONI BHAKAT PAMUA PANI UPOBHOKTA COMMITTEE
President Name
RATUL BORA
Secretary Name
AMARNATH CHETRI

About Section Officer

Name
RAJPRITOM BORA
Phone
7002363504

Water Quality details of the scheme are enlisted here.

About Water Quality

Date of Testing
N/A
PH
N/A
TDS
N/A
Iron
N/A
Arsenic/Flouride
N/A
Residual Chlorine
N/A
Bacteriological Test
N/A

Component details of the scheme are enlisted here.

About Scheme Components

Component Name
ugr
Specification
Component Name
ESR-Mild_Steel_GRP
Specification
Component Name
Submersible
Specification
Component Name
Centrifugal
Specification
Component Name
Openwell
Specification

Please click on button to view map.

Map

You need to login to evaluate a scheme.

Register

Login

Water Quality Test Report

Sample Tested Status

Total Samples Tested: 4

Chemical Testing Date: 4/24/2024 1:35:00 PM

Bacteriological Testing Date: 4/24/2024 1:35:00 PM

Water Quality Status: Safe

Remedial Action Status: --

Chemical Contamination Results

Parameter Unit Acceptable Limit Permissible Limit Value Range Status
Free residual Chlorine mg/l 0.2 1 0.300

Safe :1

> 1 Safe
Total Arsenic (As As) mg/l 0.01 No Relaxation 0.000

Safe :1

> 0.01 Safe
Iron (As Fe) mg/l 1 No Relaxation 0.210

Safe :1

> 1 Safe
Total Hardness (As CaCO3) mg/l 200 600 74.590

Safe :1

> 600 Safe
Magnesium (As Mg) mg/l 30 100 12.680

Safe :1

> 100 Safe
Calcium (as Ca) mg/l 75 200 22.620

Safe :1

> 200 Safe
Sulphate (as SO4) mg/l 200 400 0.000

Safe :1

> 400 Safe
Nitrate (as NO3) mg/l 45 No Relaxation 0.000

Safe :1

> 45 Safe
Fluoride (as F) mg/l 1 1.5 0.000

Safe :1

> 1.5 Safe
Chloride (as Cl) mg/l 250 1000 5.670

Safe :1

> 1000 Safe
Total Alkalinity (as Calcium Carbonate) mg/l 200 600 30.000

Safe :1

> 600 Safe
TDS mg/l 500 2000 52.000

Safe :1

> 2000 Safe
pH NA 6.5-8.5 No Relaxation 7.140

Safe :1

6.5-8.5 Safe
Turbidity NTU 1 5 0.000

Safe :1

> 5 Safe

Bacteriological Contamination Results

Parameter Unit Acceptable Limit Permissible Limit Value Range Status
Bacteriological (H2S test) NA Presence or Absence Presence or Absence 0.000

Safe :1

Presence or Absence Safe
E. coli CFU/100 ml Shall not be detectable in any 100 ml sample No Relaxation 0.000

Safe :1

Shall not be detectable in any 100 ml sample Safe

Sample Testing Results

Date Contaminated Found Remedial Action Location Status Taken
24-04-2024 Chemical and bacteriological both Not required Source Safe
24-01-2024 Chemical and bacteriological both Not required Source Safe
01-07-2023 Chemical and bacteriological both Not required Source Safe
23-08-2022 Chemical and bacteriological both Not required Individual Household Safe

Nearest Laboratory

Lab Name: DLL Jorhat

Type: GOVT

Address: O/O The Ex. Engr (PHE) Jorhat Div. Na-Ali Jorhat Assam 785001

Scheme Network Map

You can follow us on:

How satisfied are you with the scheme?