jjm-logo
Jal Jeevan Mission
PHED Assam
emblem
GOVERNMENT OF ASSAM
KHATOWALPARA, MAHALIPARA PWSS
KHATOWALPARA, NO.1 ALIKASH, PANIPOTA, Udalguri
Public Health Engineering Department
Tangla Division Division
Latest Water Supplied
188 KL (14-04-2025)
Cumulative Water Supplied
20469.00 KL

Basic details of the scheme are enlisted here, for further information please contact concerned officer of division / sub division

About This Scheme

Name
KHATOWALPARA, MAHALIPARA PWSS
Scheme ID
30211265
Division
Tangla Division
District
Udalguri
Block

Panchayat

UDALGURI

RATANPUR VCDC

Village

Habitation

KHATOWALPARA, NO.1 ALIKASH, PANIPOTA

KHATOWALPARA, NO.1 ALIKASH, MAHALIAPARA, PANIPOTA

Implementing Agency details of the scheme are enlisted here

About Scheme

Approved On
1st SLSSC | (2022-23)
No. of FHTC
-
Total Cost
14219000.00
State Share
1350805.00
Central Share
12157245.00
Handed Over On
2024-09-20 00:00:00

About Implementing Agency

Name of Agency
MANUJ DEBNATH
Work Order Date
2023-05-30

Jal Mitra & WUC Users details of the scheme are enlisted here

About Jal Mitra

Name
KRISHAN RABHA
Phone
6002061215

About WUC

WUC Name
KHATOWALPARA, MAHALIPARA PWSS
President Name
Krishna Boro
Secretary Name
Mridul Deka

About Section Officer

Name
Imdadul Haque
Phone
9101197229

Water Quality details of the scheme are enlisted here.

About Water Quality

Date of Testing
N/A
PH
N/A
TDS
N/A
Iron
N/A
Arsenic/Flouride
N/A
Residual Chlorine
N/A
Bacteriological Test
N/A

Component details of the scheme are enlisted here.

About Scheme Components

Component Name
Submersible
Specification
Component Name
Centrifugal
Specification

Please click on button to view map.

Map

You need to login to evaluate a scheme.

Register

Login

Water Quality Test Report

Sample Tested Status

Total Samples Tested: 13

Chemical Testing Date: 9/9/2024 3:02:00 PM

Bacteriological Testing Date: 9/9/2024 3:02:00 PM

Water Quality Status: Safe

Remedial Action Status: --

Chemical Contamination Results

Parameter Unit Acceptable Limit Permissible Limit Value Range Status
Free residual Chlorine mg/l 0.2 1 0.100

Safe :1

> 1 Safe
Total Arsenic (As As) mg/l 0.01 No Relaxation 0.000

Safe :1

> 0.01 Safe
Iron (As Fe) mg/l 1 No Relaxation 0.240

Safe :1

> 1 Safe
Total Hardness (As CaCO3) mg/l 200 600 52.640

Safe :1

> 600 Safe
Magnesium (As Mg) mg/l 30 100 8.940

Safe :1

> 100 Safe
Calcium (as Ca) mg/l 75 200 15.820

Safe :1

> 200 Safe
Sulphate (as SO4) mg/l 200 400 20.920

Safe :1

> 400 Safe
Nitrate (as NO3) mg/l 45 No Relaxation 0.710

Safe :1

> 45 Safe
Fluoride (as F) mg/l 1 1.5 0.090

Safe :1

> 1.5 Safe
Chloride (as Cl) mg/l 250 1000 9.420

Safe :1

> 1000 Safe
Total Alkalinity (as Calcium Carbonate) mg/l 200 600 84.000

Safe :1

> 600 Safe
TDS mg/l 500 2000 54.000

Safe :1

> 2000 Safe
pH NA 6.5-8.5 No Relaxation 6.960

Safe :1

6.5-8.5 Safe
Turbidity NTU 1 5 0.100

Safe :1

> 5 Safe
Colour Hazen units 5 15 2.000

Safe :1

> 15 Safe

Bacteriological Contamination Results

Parameter Unit Acceptable Limit Permissible Limit Value Range Status
E. coli CFU/100 ml Shall not be detectable in any 100 ml sample No Relaxation 0.000

Safe :1

Shall not be detectable in any 100 ml sample Safe

Sample Testing Results

Date Contaminated Found Remedial Action Location Status Taken
09-09-2024 Chemical and bacteriological both Not required Individual Household Safe
13-08-2024 Chemical and bacteriological both Not required Source Safe
11-04-2024 Chemical and bacteriological both Not required Source Safe
11-04-2024 Chemical and bacteriological both Not required Source Safe
11-04-2024 Chemical and bacteriological both Not required Source Safe
30-11-2023 Chemical and bacteriological both Not required Source Safe
30-11-2023 Chemical and bacteriological both Not required Source Safe
30-11-2023 Chemical and bacteriological both Not required Source Safe
21-06-2023 Chemical and bacteriological both Not required Source Safe
21-06-2023 Chemical and bacteriological both Not required Source Safe
21-06-2023 Chemical and bacteriological both Not required Source Safe
22-02-2023 Chemical and bacteriological both Not required Source Safe
03-02-2023 Chemical and bacteriological both Not required Source Safe

Nearest Laboratory

Lab Name: DLL Tangla

Type: GOVT

Address: o/o The Ex. Eng (PHE) Tangla Div, Dist: Udalguri, Assam, Pin: 784521

Scheme Network Map

You can follow us on:

How satisfied are you with the scheme?