jjm-logo
Jal Jeevan Mission
PHED Assam
emblem
GOVERNMENT OF ASSAM
Dui Depota maz Pathar PWSS
Duidi Pota Maz-Pathar, Sonitpur
Public Health Engineering Department
Tezpur II Division Division
Latest Water Supplied
940 KL (21-04-2025)
Cumulative Water Supplied
39238.00 KL

Basic details of the scheme are enlisted here, for further information please contact concerned officer of division / sub division

About This Scheme

Name
Dui Depota maz Pathar PWSS
Scheme ID
30172409
Division
Tezpur II Division
District
Sonitpur
Block

Panchayat

BIHAGURI

BIHAGURI NO.1

Village

Habitation

Duidi Pota Maz-Pathar

BORDOLOI CHUBA, DUIDIPOTA MASPATHER, MUSLIM PARA

Implementing Agency details of the scheme are enlisted here

About Scheme

Approved On
3rd SLSSC | (2022-23)
No. of FHTC
-
Total Cost
5600000.00
State Share
532000.00
Central Share
4788000.00
Handed Over On
2024-03-06 00:00:00

About Implementing Agency

Name of Agency
Sujashree Enterprise
Work Order Date
2023-10-12

Jal Mitra & WUC Users details of the scheme are enlisted here

About Jal Mitra

Name
Nitu Baruah
Phone
9101833403

About WUC

WUC Name
Duidipota mazarpathar PWSS
President Name
DOYAMOY BORA
Secretary Name
JUNMONI PATHAK BARUAH

About Section Officer

Name
Ratan Aich
Phone
9854290576

Water Quality details of the scheme are enlisted here.

About Water Quality

Date of Testing
N/A
PH
N/A
TDS
N/A
Iron
N/A
Arsenic/Flouride
N/A
Residual Chlorine
N/A
Bacteriological Test
N/A

Component details of the scheme are enlisted here.

About Scheme Components

No data found.

Please click on button to view map.

Map

You need to login to evaluate a scheme.

Register

Login

Water Quality Test Report

Sample Tested Status

Total Samples Tested: 1

Chemical Testing Date: 8/3/2024 5:43:00 PM

Bacteriological Testing Date: 8/3/2024 5:43:00 PM

Water Quality Status: Safe

Remedial Action Status: --

Chemical Contamination Results

Parameter Unit Acceptable Limit Permissible Limit Value Range Status
Colour Hazen units 5 15 5.000

Safe :1

> 15 Safe
Chloride (as Cl) mg/l 250 1000 19.852

Safe :1

> 1000 Safe
Total Alkalinity (as Calcium Carbonate) mg/l 200 600 25.000

Safe :1

> 600 Safe
TDS mg/l 500 2000 60.000

Safe :1

> 2000 Safe
pH NA 6.5-8.5 No Relaxation 6.680

Safe :1

6.5-8.5 Safe
Turbidity NTU 1 5 0.100

Safe :1

> 5 Safe
Fluoride (as F) mg/l 1 1.5 0.020

Safe :1

> 1.5 Safe
Nitrate (as NO3) mg/l 45 No Relaxation 5.830

Safe :1

> 45 Safe
Free residual Chlorine mg/l 0.2 1 0.100

Safe :1

> 1 Safe
Iron (As Fe) mg/l 1 No Relaxation 0.040

Safe :1

> 1 Safe
Total Arsenic (As As) mg/l 0.01 No Relaxation 0.000

Safe :1

> 0.01 Safe
Total Hardness (As CaCO3) mg/l 200 600 72.000

Safe :1

> 600 Safe
Magnesium (As Mg) mg/l 30 100 5.830

Safe :1

> 100 Safe
Calcium (as Ca) mg/l 75 200 19.240

Safe :1

> 200 Safe
Sulphate (as SO4) mg/l 200 400 5.830

Safe :1

> 400 Safe

Bacteriological Contamination Results

Parameter Unit Acceptable Limit Permissible Limit Value Range Status
E. coli CFU/100 ml Shall not be detectable in any 100 ml sample No Relaxation 0.000

Safe :1

Shall not be detectable in any 100 ml sample Safe

Sample Testing Results

Date Contaminated Found Remedial Action Location Status Taken
03-08-2024 Chemical and bacteriological both Not required Source Safe

Nearest Laboratory

Lab Name: DLL Sonitpur

Type: GOVT

Address: o/o The Executive Engineer (PHE) Tezpur Div No 1, Rubber Bagan, Tezpur, Assam, Pin: 784001

Scheme Network Map

You can follow us on:

How satisfied are you with the scheme?