jjm-logo
Jal Jeevan Mission
PHED Assam
emblem
GOVERNMENT OF ASSAM
GANDHI GAON PWSS
MORANGI BAGAN, Golaghat
Public Health Engineering Department
Golaghat Division Division
Latest Water Supplied
22 KL (30-05-2025)
Cumulative Water Supplied
6563.00 KL

Basic details of the scheme are enlisted here, for further information please contact concerned officer of division / sub division

About This Scheme

Name
GANDHI GAON PWSS
Scheme ID
30184868
Division
Golaghat Division
District
Golaghat
Block

Panchayat

MORONGI

PANKA

Village

Habitation

MORANGI BAGAN

NOI KANOR LINE

Implementing Agency details of the scheme are enlisted here

About Scheme

Approved On
2nd SLSSC | (2022-23)
No. of FHTC
-
Total Cost
7508000.00
State Share
713260.00
Central Share
6419340.00
Handed Over On
2024-07-19 00:00:00

About Implementing Agency

Name of Agency
PURVANCHAL ENTERPRISE
Work Order Date
2023-07-21

Jal Mitra & WUC Users details of the scheme are enlisted here

About Jal Mitra

Name
HOREN DAS
Phone
6000600949

About WUC

WUC Name
GANDHI GAON PWSS
President Name
BISESWAR DAS
Secretary Name
JAYANTA DAS

About Section Officer

Name
BIJU HAZARIKA
Phone
9085531449

Water Quality details of the scheme are enlisted here.

About Water Quality

Date of Testing
N/A
PH
N/A
TDS
N/A
Iron
N/A
Arsenic/Flouride
N/A
Residual Chlorine
N/A
Bacteriological Test
N/A

Component details of the scheme are enlisted here.

About Scheme Components

No data found.

Please click on button to view map.

Map

You need to login to evaluate a scheme.

Register

Login

Water Quality Test Report

Sample Tested Status

Total Samples Tested: 37

Chemical Testing Date: 2/21/2025 3:30:00 PM

Bacteriological Testing Date: 5/18/2024 11:05:00 AM

Water Quality Status: Safe

Remedial Action Status: --

Chemical Contamination Results

Parameter Unit Acceptable Limit Permissible Limit Value Range Status
Colour Hazen units 5 15 5.000

Safe :1

> 15 Safe
pH NA 6.5-8.5 No Relaxation 6.720

Safe :1

6.5-8.5 Safe
TDS mg/l 500 2000 95.000

Safe :1

> 2000 Safe
Total Alkalinity (as Calcium Carbonate) mg/l 200 600 152.000

Safe :1

> 600 Safe
Chloride (as Cl) mg/l 250 1000 21.970

Safe :1

> 1000 Safe
Fluoride (as F) mg/l 1 1.5 0.080

Safe :1

> 1.5 Safe
Nitrate (as NO3) mg/l 45 No Relaxation 0.500

Safe :1

> 45 Safe
Sulphate (as SO4) mg/l 200 400 7.410

Safe :1

> 400 Safe
Total Hardness (As CaCO3) mg/l 200 600 120.000

Safe :1

> 600 Safe
Iron (As Fe) mg/l 1 No Relaxation 0.800

Safe :1

> 1 Safe
Total Arsenic (As As) mg/l 0.01 No Relaxation 0.000

Safe :1

> 0.01 Safe
Free residual Chlorine mg/l 0.2 1 0.200

Safe :1

> 1 Safe

Bacteriological Contamination Results

Parameter Unit Acceptable Limit Permissible Limit Value Range Status
E. coli CFU/100 ml Shall not be detectable in any 100 ml sample No Relaxation 0.000

Safe :1

Shall not be detectable in any 100 ml sample Safe
Bacteriological (H2S test) NA Presence or Absence Presence or Absence 0.000

Safe :1

Presence or Absence Safe

Sample Testing Results

Date Contaminated Found Remedial Action Location Status Taken
21-02-2025 Chemical Not required Source Safe
21-02-2025 Chemical Not required Source Safe
02-12-2024 Chemical Not required Source Safe
02-12-2024 Chemical Not required Source Safe
01-11-2024 Chemical Not required Source Safe
25-10-2024 Chemical Not required Source Safe
25-10-2024 Chemical Not required Source Safe
25-10-2024 Chemical Yes Source Unsafe
25-10-2024 Chemical Not required Source Safe
18-05-2024 Chemical and bacteriological both Not required Individual Household Safe
17-05-2024 Chemical and bacteriological both Not required Individual Household Safe
17-05-2024 Chemical and bacteriological both Not required Individual Household Safe
17-05-2024 Chemical and bacteriological both Not required Individual Household Safe
17-05-2024 Chemical and bacteriological both Not required Individual Household Safe
02-01-2024 Bacteriological Not required Source Safe
02-01-2024 Bacteriological Not required Source Safe
02-01-2024 Bacteriological Not required Source Safe
02-01-2024 Bacteriological Not required Source Safe
31-12-2023 Bacteriological Not required Source Safe
30-05-2023 Bacteriological Not required Source Safe
27-05-2023 Chemical and bacteriological both Not required Source Safe
27-05-2023 Chemical and bacteriological both Not required Source Safe
27-05-2023 Chemical and bacteriological both Not required Source Safe
27-05-2023 Chemical and bacteriological both Not required Source Safe
27-05-2023 Chemical and bacteriological both Not required Source Safe
13-04-2023 Chemical and bacteriological both Not required Source Safe
13-04-2023 Chemical and bacteriological both Not required Source Safe
27-02-2023 Chemical and bacteriological both Not required Source Safe
25-02-2023 Chemical and bacteriological both Not required Source Safe
24-02-2023 Chemical and bacteriological both Not required Source Safe
24-02-2023 Chemical and bacteriological both Not required Source Safe
08-12-2022 Bacteriological Not required Source Safe
08-12-2022 Bacteriological Not required Source Safe
07-12-2022 Bacteriological Not required Source Safe
07-12-2022 Bacteriological Not required Source Safe
07-12-2022 Bacteriological Not required Source Safe
07-12-2022 Bacteriological Not required Source Safe

Nearest Laboratory

Lab Name: DLL Golaghat

Type: GOVT

Address: O/O The Executive Engineer (PHE), Golaghat Div, Golaghat, Sati Jaimoti Path Jonaki Nagar, Golaghat, Assam Pin: 785621

Scheme Network Map

You can follow us on:

How satisfied are you with the scheme?