jjm-logo
Jal Jeevan Mission
PHED Assam
emblem
GOVERNMENT OF ASSAM
Natun Rongagorah PWSS
GOTONG GAON, NO-4 FS.RANGAGARA TE.NATUNGAON, Tinsukia
Public Health Engineering Department
Tinisukia Division
Latest Water Supplied
39 KL (27-01-2025)
Cumulative Water Supplied
895.00 KL

Basic details of the scheme are enlisted here, for further information please contact concerned officer of division / sub division

About This Scheme

Name
Natun Rongagorah PWSS
Scheme ID
30200853
Division
Tinisukia Division
District
Tinsukia
Block

Panchayat

GUIJAN

GOTTONG

Village

Habitation

GOTONG GAON, NO-4 FS.RANGAGARA TE.NATUNGAON

GAMIRI GHAT, KHARIA BASTI, LIMBUGURI CHUCK

Implementing Agency details of the scheme are enlisted here

About Scheme

Approved On
3rd SLSSC | (2022-23)
No. of FHTC
173
Total Cost
13830300.00
State Share
1313879.00
Central Share
11824907.00
Handed Over On
2024-06-10 00:00:00

About Implementing Agency

Name of Agency
PRACHURYA NEOG
Work Order Date
-

Jal Mitra & WUC Users details of the scheme are enlisted here

About Jal Mitra

Name
PRIYANKA BORUAH
Phone
9957298505

About Section Officer

Name
ANINDITA BHUYAN
Phone
9365099565

Water Quality details of the scheme are enlisted here.

About Water Quality

Date of Testing
N/A
PH
N/A
TDS
N/A
Iron
N/A
Arsenic/Flouride
N/A
Residual Chlorine
N/A
Bacteriological Test
N/A

Component details of the scheme are enlisted here.

About Scheme Components

Asset Category
Pump
Component Name
Submersible
Capacity
3.00 HP
Specification
Asset Category
Pump
Component Name
Centrifugal
Capacity
5.00 HP
Specification

Please click on button to view map.

Map

You need to login to evaluate a scheme.

Register

Login

Water Quality Test Report

Sample Tested Status

Total Samples Tested: 12

Chemical Testing Date: 5/14/2025 1:10:00 PM

Bacteriological Testing Date: 5/14/2025 1:10:00 PM

Water Quality Status: Safe

Remedial Action Status: --

Chemical Contamination Results

Parameter Unit Acceptable Limit Permissible Limit Value Range Status
Colour Hazen units 5 15 10.000

Safe :1

> 15 Safe
Turbidity NTU 1 5 3.110

Safe :1

> 5 Safe
pH NA 6.5-8.5 No Relaxation 7.050

Safe :1

6.5-8.5 Safe
TDS mg/l 500 2000 170.000

Safe :1

> 2000 Safe
Total Alkalinity (as Calcium Carbonate) mg/l 200 600 132.000

Safe :1

> 600 Safe
Chloride (as Cl) mg/l 250 1000 42.200

Safe :1

> 1000 Safe
Fluoride (as F) mg/l 1 1.5 0.210

Safe :1

> 1.5 Safe
Nitrate (as NO3) mg/l 45 No Relaxation 0.000

Safe :1

> 45 Safe
Sulphate (as SO4) mg/l 200 400 7.040

Safe :1

> 400 Safe
Calcium (as Ca) mg/l 75 200 60.250

Safe :1

> 200 Safe
Magnesium (As Mg) mg/l 30 100 13.260

Safe :1

> 100 Safe
Total Hardness (As CaCO3) mg/l 200 600 132.000

Safe :1

> 600 Safe
Iron (As Fe) mg/l 1 No Relaxation 0.600

Safe :1

> 1 Safe
Total Arsenic (As As) mg/l 0.01 No Relaxation 0.000

Safe :1

> 0.01 Safe
Free residual Chlorine mg/l 0.2 1 0.000

Safe :1

> 1 Safe

Bacteriological Contamination Results

Parameter Unit Acceptable Limit Permissible Limit Value Range Status
E. coli CFU/100 ml Shall not be detectable in any 100 ml sample No Relaxation 0.000

Safe :1

Shall not be detectable in any 100 ml sample Safe
Total coliform CFU/ 100 ml Shall not be detectable in any 100 ml sample No Relaxation 0.000

Safe :1

Shall not be detectable in any 100 ml sample Safe

Sample Testing Results

Date Contaminated Found Remedial Action Location Status Taken
14-05-2025 Chemical and bacteriological both Not required Source Safe
21-01-2025 Chemical and bacteriological both Not required Source Safe
20-01-2025 Chemical and bacteriological both Not required Source Safe
20-01-2025 Chemical and bacteriological both Not required Source Safe
20-01-2025 Chemical and bacteriological both Not required Source Safe
15-05-2024 Bacteriological Not required Source Safe
11-05-2024 Bacteriological Not required Source Safe
08-05-2024 Bacteriological Not required Source Safe
13-01-2024 Chemical and bacteriological both Not required Source Safe
13-01-2024 Chemical and bacteriological both Not required Source Safe
13-01-2024 Chemical and bacteriological both Not required Source Safe
13-01-2024 Chemical and bacteriological both Not required Source Safe

Nearest Laboratory

Lab Name: DLL Tinsukia

Type: GOVT

Address: o/o Executive Engineer (PHE), Tinsukia Div., Borguri, Dist: Tinsukia, Assam, Pin: 786126

Scheme Network Map

Submit your grievance through:

You can follow us on:

How satisfied are you with the scheme?