jjm-logo
Jal Jeevan Mission
PHED Assam
emblem
GOVERNMENT OF ASSAM
DHUMKUNDA PWSS
DANGARI T.E. 131 NO. FS., Tinsukia
Public Health Engineering Department
Tinisukia Division
Latest Water Supplied
Data Not Appropriate KL ()
Cumulative Water Supplied
N/A

Basic details of the scheme are enlisted here, for further information please contact concerned officer of division / sub division

About This Scheme

Name
DHUMKUNDA PWSS
Scheme ID
30020439
Division
Tinisukia Division
District
Tinsukia
Block

Panchayat

KAKAPATHAR

RONGAJAN

Village

Habitation

DANGARI T.E. 131 NO. FS.

DHUMKUNDA

Implementing Agency details of the scheme are enlisted here

About Scheme

Approved On
3rd SLSSC | (2022-23)
No. of FHTC
210
Total Cost
9630700.00
State Share
914917.00
Central Share
8234249.00
Handed Over On
2023-07-24 00:00:00

About Implementing Agency

Name of Agency
Vinay Bhardwaj
Work Order Date
-

Jal Mitra & WUC Users details of the scheme are enlisted here

About Jal Mitra

Name
Roshan Mundu
Phone
8822033211

About WUC

WUC Name
DHUMKUNDA PWSS
President Name
JUNASH MUNDU
Secretary Name
DAUGH KAWA

About Section Officer

Name
PARASHMONI GOGOI
Phone
8135961797

Water Quality details of the scheme are enlisted here.

About Water Quality

Date of Testing
N/A
PH
N/A
TDS
N/A
Iron
N/A
Arsenic/Flouride
N/A
Residual Chlorine
N/A
Bacteriological Test
N/A

Component details of the scheme are enlisted here.

About Scheme Components

Asset Category
Pump
Component Name
Centrifugal
Capacity
3.00 HP
Specification

Please click on button to view map.

Map

You need to login to evaluate a scheme.

Register

Login

Water Quality Test Report

Sample Tested Status

Total Samples Tested: 23

Chemical Testing Date: 12/24/2024 4:45:00 PM

Bacteriological Testing Date: 6/24/2024 1:50:00 PM

Water Quality Status: Safe

Remedial Action Status: --

Chemical Contamination Results

Parameter Unit Acceptable Limit Permissible Limit Value Range Status
Fluoride (as F) mg/l 1 1.5 0.000

Safe :1

> 1.5 Safe
Sulphate (as SO4) mg/l 200 400 0.000

Safe :1

> 400 Safe
Calcium (as Ca) mg/l 75 200 10.420

Safe :1

> 200 Safe
Magnesium (As Mg) mg/l 30 100 8.262

Safe :1

> 100 Safe
Total Hardness (As CaCO3) mg/l 200 600 60.000

Safe :1

> 600 Safe
Iron (As Fe) mg/l 1 No Relaxation 0.051

Safe :1

> 1 Safe
Total Arsenic (As As) mg/l 0.01 No Relaxation 0.000

Safe :1

> 0.01 Safe
Free residual Chlorine mg/l 0.2 1 0.400

Safe :1

> 1 Safe
Colour Hazen units 5 15 1.000

Safe :1

> 15 Safe
Turbidity NTU 1 5 0.800

Safe :1

> 5 Safe
pH NA 6.5-8.5 No Relaxation 7.080

Safe :1

6.5-8.5 Safe
TDS mg/l 500 2000 64.000

Safe :1

> 2000 Safe
Total Alkalinity (as Calcium Carbonate) mg/l 200 600 78.000

Safe :1

> 600 Safe
Chloride (as Cl) mg/l 250 1000 22.690

Safe :1

> 1000 Safe

Bacteriological Contamination Results

Parameter Unit Acceptable Limit Permissible Limit Value Range Status
E. coli CFU/100 ml Shall not be detectable in any 100 ml sample No Relaxation 0.000

Safe :1

Shall not be detectable in any 100 ml sample Safe

Sample Testing Results

Date Contaminated Found Remedial Action Location Status Taken
24-12-2024 Chemical Not required Source Safe
24-12-2024 Chemical Not required Source Safe
10-12-2024 Chemical Not required Source Safe
29-11-2024 Chemical Not required Source Safe
29-11-2024 Chemical Not required Source Safe
24-06-2024 Bacteriological Not required Source Safe
24-06-2024 Bacteriological Not required Source Safe
18-06-2024 Chemical and bacteriological both Not required Source Safe
07-06-2024 Chemical and bacteriological both Not required Source Safe
28-05-2024 Bacteriological Not required Source Safe
18-03-2024 Chemical Not required Source Safe
18-03-2024 Chemical Not required Source Safe
17-02-2024 Chemical and bacteriological both Yes Source Unsafe
17-02-2024 Chemical and bacteriological both Not required Source Safe
17-02-2024 Chemical and bacteriological both Yes Source Unsafe
17-02-2024 Chemical and bacteriological both Not required Source Safe
20-01-2024 Chemical and bacteriological both Not required Source Safe
20-01-2024 Chemical and bacteriological both Yes Source Unsafe
25-08-2023 Chemical and bacteriological both Not required Source Safe
17-08-2023 Chemical and bacteriological both Not required Source Safe
17-08-2023 Chemical and bacteriological both Not required Source Safe
05-08-2023 Chemical and bacteriological both Not required Individual Household Safe
05-08-2023 Chemical and bacteriological both Not required Individual Household Safe

Nearest Laboratory

Lab Name: DLL Tinsukia

Type: GOVT

Address: o/o Executive Engineer (PHE), Tinsukia Div., Borguri, Dist: Tinsukia, Assam, Pin: 786126

Scheme Network Map

Submit your grievance through:

You can follow us on:

How satisfied are you with the scheme?