jjm-logo
Jal Jeevan Mission
PHED Assam
emblem
GOVERNMENT OF ASSAM
RETROFITTING OF PITAMBAR HAT BAJALI-II PWSS
PITAMBAR HAT BAJALI, Kamrup
Public Health Engineering Department
Rangia Division Division
Latest Water Supplied
Data Not Appropriate KL ()
Cumulative Water Supplied
N/A

Basic details of the scheme are enlisted here, for further information please contact concerned officer of division / sub division

About This Scheme

Name
RETROFITTING OF PITAMBAR HAT BAJALI-II PWSS
Scheme ID
0008226519
Division
Rangia Division
District
Kamrup
Block

Panchayat

RANGIA (PART)

JAYANTIPUR

Village

Habitation

PITAMBAR HAT BAJALI

BORO SUBA, GOSAIKHAT, KUMARPARA, SARA SUBA

Implementing Agency details of the scheme are enlisted here

About Scheme

Approved On
2nd SLSSC | (2020-21)
No. of FHTC
410.00
Total Cost
9250000.00
State Share
879000.00
Central Share
7909000.00
Handed Over On
2022-11-10 00:00:00

About Implementing Agency

Name of Agency
SAIDUL ISLAM
Work Order Date
2021-01-11

Jal Mitra & WUC Users details of the scheme are enlisted here

About Jal Mitra

Name
DIPAK KUMAR
Phone
9954531179

About WUC

WUC Name
Pitanbar Hat Bajali No2 Pani Upabhogta Committee
President Name
Rita Baishya
Secretary Name
Paladhar Kumar

About Section Officer

Name
CHANDRA KANTA DAS
Phone
9365118613

Water Quality details of the scheme are enlisted here.

About Water Quality

Date of Testing
N/A
PH
N/A
TDS
N/A
Iron
N/A
Arsenic/Flouride
N/A
Residual Chlorine
N/A
Bacteriological Test
N/A

Component details of the scheme are enlisted here.

About Scheme Components

No data found.

Please click on button to view map.

Map

You need to login to evaluate a scheme.

Register

Login

Water Quality Test Report

Sample Tested Status

Total Samples Tested: 22

Chemical Testing Date: 2/29/2024 1:28:00 PM

Bacteriological Testing Date: 2/29/2024 1:28:00 PM

Water Quality Status: Safe

Remedial Action Status: --

Chemical Contamination Results

Parameter Unit Acceptable Limit Permissible Limit Value Range Status
Colour Hazen units 5 15 10.000

Safe :1

> 15 Safe
Turbidity NTU 1 5 0.800

Safe :1

> 5 Safe
pH NA 6.5-8.5 No Relaxation 7.430

Safe :1

6.5-8.5 Safe
TDS mg/l 500 2000 127.000

Safe :1

> 2000 Safe
Total Alkalinity (as Calcium Carbonate) mg/l 200 600 116.000

Safe :1

> 600 Safe
Chloride (as Cl) mg/l 250 1000 17.020

Safe :1

> 1000 Safe
Fluoride (as F) mg/l 1 1.5 0.804

Safe :1

> 1.5 Safe
Nitrate (as NO3) mg/l 45 No Relaxation 0.741

Safe :1

> 45 Safe
Sulphate (as SO4) mg/l 200 400 8.648

Safe :1

> 400 Safe
Calcium (as Ca) mg/l 75 200 21.620

Safe :1

> 200 Safe
Total Hardness (As CaCO3) mg/l 200 600 98.000

Safe :1

> 600 Safe
Iron (As Fe) mg/l 1 No Relaxation 0.671

Safe :1

> 1 Safe
Total Arsenic (As As) mg/l 0.01 No Relaxation 0.000

Safe :1

> 0.01 Safe
Free residual Chlorine mg/l 0.2 1 0.000

Safe :1

> 1 Safe

Bacteriological Contamination Results

Parameter Unit Acceptable Limit Permissible Limit Value Range Status
E. coli CFU/100 ml Shall not be detectable in any 100 ml sample No Relaxation 0.000

Safe :1

Shall not be detectable in any 100 ml sample Safe

Sample Testing Results

Date Contaminated Found Remedial Action Location Status Taken
29-02-2024 Chemical and bacteriological both Not required Source Safe
29-02-2024 Chemical and bacteriological both Not required Source Safe
29-02-2024 Chemical and bacteriological both Not required Source Safe
05-02-2024 Chemical and bacteriological both Not required Source Safe
11-01-2024 Bacteriological Not required Source Safe
11-01-2024 Bacteriological Not required Source Safe
11-01-2024 Bacteriological Not required Source Safe
08-11-2023 Chemical and bacteriological both Not required Source Safe
14-09-2023 Chemical and bacteriological both Not required Individual Household Safe
14-09-2023 Chemical and bacteriological both Not required Individual Household Safe
14-09-2023 Chemical and bacteriological both Not required Individual Household Safe
20-07-2023 Chemical and bacteriological both Not required Individual Household Safe
16-07-2023 Chemical and bacteriological both Not required Individual Household Safe
16-07-2023 Chemical and bacteriological both Not required Individual Household Safe
16-07-2023 Chemical and bacteriological both Not required Individual Household Safe
16-07-2023 Chemical and bacteriological both Not required Individual Household Safe
16-07-2023 Chemical and bacteriological both Not required Individual Household Safe
16-07-2023 Chemical and bacteriological both Not required Individual Household Safe
16-07-2023 Chemical and bacteriological both Not required Individual Household Safe
15-02-2023 Chemical Not required Individual Household Safe
15-02-2023 Chemical Not required Individual Household Safe
15-02-2023 Chemical Not required Individual Household Safe

Nearest Laboratory

Lab Name: DLL Kamrup

Type: GOVT

Address: o/o The Executive Engineer (PHE) Guwahati Div 1, Bamunimaidam, Guwahati 21

Scheme Network Map

You can follow us on:

How satisfied are you with the scheme?